All installations and services must be performed by qualified service personnel.

28

Anticipators for the cooling operation are generally pre-set by the thermostat
manufacturer and require no adjustment.



5. Blower Motor Speed Wiring


:

TURN OFF THE ELECTRICAL POWER to the furnace before

attempting to change blower speed wiring.

The blower motor is factory wired to the ignition control with standard heating
and cooling speeds pre-selected.
When changing motor speeds, simply switch the wire from the needed speed to
either the heating or cooling terminal as applicable on the module to obtain the
desired airflow. The wires for the unused speeds should then be reconnected to
the module in the “park” positions.

Figure 8: Blower and Control Panel

The option switches on the W/R integrated control are used to determine the
length of the heat delay-to-fan-on and delay –to-fan-off periods. The following
tables show the time periods that will result from the various switch positions.

SPEEDS

PARK TERMINALS

FOR UNUSED

234
1

ON

GREEN

12

0v

24

v

GREEN

CAPACITOR

TERMINAL HEATING SPEED

TERMINAL COOLING SPEED

TRANSFORMER

NOTE:
MHA1-50,75,100,125
MDA1-50,100
USE LOW SPEED FOR HEATING

MDA1-75,125
USE MED-LOW SPEED FOR HEATING

MHA/MDA1-50 HAS A
3 SPEED MOTOR

HIGH SPEED (BLACK)

LOW SPEED (RED)

MED-LOW SPEED (BLUE)

MED-HIGH SPEED (YELLOW)

COMMON (WHITE)

OPTIONAL FAN

DELAY SWITCHES

EAC

HUMIDIFIER

EAC - COMMON

HUMIDIFIER - COMMON