APPENDIX B: SEQUENCE OF OPERATIONS

A. Sequence of Operations for Heating System

Control System Action

Ignition control module

energized,draft inducer starts.

After ignitor warm-up, the

automatic gas control valve

is energized to open.

Mode of Operation

Standby

(At any time the gas

valve is not energized)

Start

Start trial for

ignition

Continous safe operation check. If
flame simulation condition present

or roll-out switch opens,system

energizes inducer fan and circulator

blower at high speed until situation

correction occurs.

Thermostat calls for heat,

contacts close

Pressure switch senses

adequate pressure,

contacts close.

On power interruption, system

shuts off, restarts when

power is restored.

If flame is not detected, the

gas valve is de-energized,

the ignitor is turned off and

the ignition control module

goes into the "Retry" sequence.

Power is applied to the hot

surface ignitor. Ignitor warms-

up for 20 seconds.

Flame must be detected

within 4 seconds. If flame

detected, the delay-to-fan-

on time begins (45 seconds)

The retry sequence

provides a 60 second

wait before ignition retry.