RISCO Group SMPS 3A User Manual
Page 13
SMPS - Installation Guide
13
Installer Programming Menu
Function
Quick Key
Description
Add/Delete
Power
Supply
Module:
[7] [1] [4]
Selection of new type: PS02, followed by
selection of Bell/Speaker (if exists) and
assigning to partition.
Add/Delete
Utility
Output
Module:
[7] [1] [3]
New type: UO02
A Two-output relay module.
User Programming Menu
Function
Quick Key
Description
Overload
Restore
[2] [0] [2]
NOTE:
Performed only if Aux. output is overloaded and
then switched off, code is required and the
relevant SMPS is selected.
The Grand Master/Installer/Sub-
installer/Manager can use this option to
restore the Aux. power (If overload
condition is still present, disconnection of
all loads from AUX. output is required!).
View
Trouble
[3] [1]
Trouble messages dedicated to the SMPS:
Potential overload: The SMSP has
detected a potential current overload when
calculating the total expected current
consumption from the siren and the Aux.
outputs.
Overload: The total current consumption
from the Aux. and siren outputs exceed
3A.
Battery
[4] [CODE] [2]
Tests the standby battery of the pre-
selected SMPS. Battery voltage of the
relevant SMPS is displayed on the LCD.