beautypg.com

Venting – Empire Comfort Systems BVD36FP32 User Manual

Page 12

background image

Page 12

19400-3-0406

Vent Runs

In planning the installation for the fireplace, it is necessary to install

certain components before the appliance is completely positioned

and installed. These include the vent system, gas piping for the

appliance, Fresh Air Kit, and the electrical wiring. (The fan option

is available for louvered models only. Electric ignition models will

require electrical service to junction box).
The appliance can be mounted on any of the following surfaces:

1. A flat, hard combustible (burnable) surface.

2. A raised wooden platform.

3. Four (4) corner supports. (Example: Four (4) concrete masonry

blocks.) These supports must be positioned so they contact all

four (4) perimeter edges on the bottom of the unit.

Locate and mark the center point of the vent pipe using a nail on

the underside of the roof. Drive the nail through the center point.

Mark the outline of the roof hole around this center point.
NOTE: Size of the roof hole dimensions depend on the pitch of

the roof. There must be a 1 inch clearance (25mm) to the

vertical pipe sections. This clearance is to all combustible

material.

Cover the opening of the vent pipe and cut and frame the roof hole.

Use framing lumber the same size as the roof rafters and install the

frame securely. Flashing anchored to frame must withstand high

winds. The storm collar is placed over this joint to make a water-

tight seal. Non-hardening sealant should be used to completely

seal this flashing installation.
Determining Minimum Vent Height Above the Roof.
WARNING: Major U.S. building codes specify minimum

chimney and/or vent height above the roof top. These

minimum heights are necessary in the interest of safety. These

specifications are summarized in Figures 14 and 15.

Figure 13

Note that for steep roof pitches, the vent height must be increased.

In high wind conditions, nearby trees, adjoining roof lines, steep

pitched roofs, and other similar factors can result in poor draft,

or down-drafting. In these cases, increasing the vent height may

solve this problem.
General Maintenance

Conduct an inspection of the venting system semi-annually.

Recommended areas to inspect are as follows:

1. Check areas of the venting system which are exposed to the

elements for corrosion. These will appear as rust spots or

streaks and, in extreme cases, holes. These components should

immediately be replaced.

2. Remove the cap and shine a flashlight down the vent. Remove

any bird nests or other foreign material.

3. Check for evidence of excessive condensate, such as water

droplets forming in the inner liner and subsequently dripping

out at joints. Condensate can cause corrosion of caps, pipe and

fittings. It may be caused by having excessive lateral runs, too

many elbows and exterior portions of the system being exposed

to cold weather.

4. Inspect joints to verify that no pipe sections or fittings have been

disturbed and, consequently, loosened. Also, check mechanical

supports, such as wall straps or plumbers’ tape for rigidity.

A removable panel or other means must be provided in the enclosure

for visual inspection of the flue connection.
NOTE: This also pertains to vertical vent systems installed on the

outside of the building.
Installing the Vent System in a Chase

A chase is a vertical box-like structure built to enclose the gas

appliance and/or it’s vent system. Vertical vent runs on the outside

of a building may be, but are not required to be installed inside

a chase.
CAUTION: Treatment of firestop spacers and construction of

the chase may vary with the type of building. These instructions

are not substitutes for the requirements of local building

codes. Therefore, your local building codes must be checked

to determine the requirements for these steps.
NOTE:
When installing this vent system in a chase, it is always

good building practice to insulate the chase as you would the

outside walls of your home. This is especially important for cold

climate installations. Upon completion of building your chase

framing, install the vent system by following the instructions in

this manual. Remember to build the chase large enough so that

minimum clearance of combustible materials (including insulation)

to the vent system are maintained.

WARNING! This appliance must not be connected to a

chimney flue servicing a separate solid fuel or gas fuel

burning appliance.

VENT CAP

GAS VENT

H

LOWEST

DISCHARGE

OPENING

H (Min.) - Minimum height from

roof to lowest discharge opening

ROOF PITCH IS X/12

ROOF PITCH

H (Min.)

Flat to 6/12

12" (305 mm)

6/12 to 7/12

15" (381 mm)

Over 7/12 to 8/12

18" (457 mm)

Over 8/12 to 16/12

24" (610 mm)

Over 16/12 to 21/12

36" (914 mm)

VENTING

This manual is related to the following products: