CAC Cassette Evaporator

START -UP FOR WALL THERMOSTAT CONTROL

• Adding water will activate the float switch

and the pump. Water must flow regular-

Figure #4

7. To check the operation of the condensate

pump remove an adjacent ceiling tile to

access the condensate pump access:

• Insert a squeeze water bottle nozzle

through the opening in the condensate

pump access panel and fill drain pan.

Refer to Figure #4.

ly with condensate pump energized. If

water does not, check the pipe slope or

see if there are any pipe restrictions.

8. Ensure that all covers, panels and fil-

ters are in place and discharge louvers

are correctly positioned.

9. Turn the system power on and set the

cooling mode to the lowest thermostat

set point to run the compressor.

NOTE: The unit is equipped with a

safety switch that will activate the

pump when the condensate reaches

a critical level. The safety switch will

also de-energize the compressor if the

water level becomes too high.

10. Repeat the above procedure for all

Cassettes in the same systems.