Product Description

1

1.0

P

RODUCT

D

ESCRIPTION

1.1

Prop Fan Condensing Units

Liebert propeller fan condensing units are available in a range of sizes and configurations to offer

flexibility in designing a precision environmental control system. The appropriate propeller fan con-

densing unit paired with a corresponding Liebert fan coil evaporator model such as Liebert Data-

Mate, Liebert Mini-Mate2 or Liebert Challenger 3000 is an effective solution for your environmental

control application requirements.
Split system condensing units are connected to the evaporator unit by two refrigerant lines (four in

8-ton systems) and a low-voltage control cable. The condensing unit requires a separate power source

and power disconnect switch.

1.1.1 Base System 95°F (35°C) Ambient Models

The heart of the refrigeration system is a quiet, high efficiency scroll compressor with internal vibra-

tion isolation mountings, pressure safety controls and built-in overload protection. Standard features

include crankcase heater, high pressure switch, condenser coil, sight glass, filter drier, hot gas bypass

system with liquid quenching valve, direct drive propeller fan and motor, and Liebert Lee-Temp flood-

back head pressure control. These models are designed to provide catalog capacity of the appropriate

evaporator section up to 95°F (35°C) outside ambient temperature.

1.1.2 105°F (41°C) Ambient Models

These models contain similar components to the base models except the coils and fans are sized to

provide catalog capacity of the appropriate evaporator section up to 105°F (41°C) outside ambient

temperature.

1.1.3 Quiet-Line Models

These models contain similar components to the base models except the coils and fans are sized to

provide catalog capacity of the appropriate evaporator section up to 95°F (35°C) outside ambient tem-

perature with a noise level of less than 58 dBA.

1.2

Optional Equipment

1.2.1 Coated Coil

This option provides a phenolic coating for the condenser coil (extended lead time is required for this

option; consult factory).

1.2.2 Pre-Charged Refrigeration Line Sets

For efficient condenser/evaporator connection, factory pre-charged line sets with quick connect fit-

tings are available in 15-ft. and 30-ft. (4.5m and 9m) lengths. Each set includes an insulated copper

suction line and copper liquid line, both charged with R-407C refrigerant and sealed. Line sets are

only available for 1 to 3.5 Ton Units.

1.2.3 Refrigerant Line Sweat Adapter Kit

This kit includes the compatible fittings required (two for the insulated suction line and two for the liq-

uid line) when using field-supplied interconnecting refrigerant lines instead of the pre-charged line sets.

1.2.4 277V Step-Down Transformer

A 37.5A, 277V step-down transformer is available for 1-to 3-Ton 60Hz condensing units needing

277/1/60 input power. Apply this transformer to a 208/230/1/60 condensing unit. The transformer is

coated with epoxy and contained in an enclosed, non-ventilated electrical box with adaptable mount-

ing brackets.