Figure 6 general piping arrangement, Figure 6, General piping arrangement – Emerson Precision Cooling For Business-Critical Continuity Figure i User Manual
Page 12
Installation
8
Figure 6
General piping arrangement
Pressure Balancing
Valve
DPN000129 REV 1
Condenser
Coil
High Pressure
Switch
Compressor *
Hot Gas Bypass
Solenoid Valve
Hot Gas Bypass
Control Valve
3 - Way Head
Pressure
Control Valve
Check Valve
Liquid Injection
Valve Bulb
Pressure Relief Valve
Sight
Glass
Liebert Lee-Temp
Receiver
Liquid Line
Solenoid Valve
Liquid Line Male Quick
Connect Coupling
Liquid Injection
Valve
Suction Line
Male Quick
Connect Coupling
SINGLE CIRCUIT SHOWN
SINGLE CIRCUIT = 1 - 5 Tons
DUAL CIRCUIT = 8 Tons
Receiver Heater
Pressure Limiting
Switch
* Reciprocating compressor 1 Ton, 60Hz
Scroll compressor 1 Ton, 50Hz and 1-1/2 to 8 Tons