KACO blueplanet 1502x User Manual
Page 8
Page 8
blueplanet Installation Instructions 1502x - 5002x
Inverter – Mechanical and technical data
Model
1502x
2502x
3502x
5002x
Visual displays
LEDs: PV generator (green)
Grid-feed (green)
Fault (red)
LCD (2 x 16 characters)
Controls
2 keys for display operation and configuration of parameters
Connections
Cable connection via conduit fittings using ¾” or ½” blind plug Terminals accept up to AWG 10, 75’C,
copper wire.
Interfaces
RS485, S0, error transmitting relay
Ambient tempera-
ture
–4 °F ... +140 °F
(> 104 °F power derating)
–13 °F ... +140 °F
(> 104 °F power derating)
Internal
Temperature
monitoring
> 167 °F temperature-dependent power limiting
> 185 °F disconnection from the grid
Max. humidity
95 % (not-condensing)
Cooling
Free convection (no fan
)
Free convection (fan assist)
Protection class
NEMA-3R
Noise emission
< 35 dB
(noiseless)
< 35 dB
(noiseless)
< 35 dB
(noiseless)
<45 dB
(fan operation)
Housing
Aluminium wall-mounted housing
Dimensions W x
D x H
14 x 8
1/4
x 17
6/8
in.
14 x 8
1/4
x 19
6/8
in.
14 x 9
1/4
x
23
6/8
in.
14 x 9
1/4
x 23
6/8
in.
Weight
32 lbs
42 lbs
59 lbs
60 lbs
Section 3 ·
Technical Data