blueplanet Installation Instructions 1502x - 5002x

Page 19

Section 5 ·

Installation and Start-Up

!

DANGER

Risk of electric shock at live connections.

Check that the power lead is voltage-free before inserting it

into the inverter

!

WARNING

To reduce the risk of fire, connect only to a circuit provided

with the required branch-circuit overcurrent device sized in

accordance with the National Electrical Code, ANSI/NFPA 70.

The maximum size overcurrent device shall not be more than

15 A for the 1502x, 20 A for the 2502x, 25 A for the 3502x and

and 30 A for the 5002x.

NOTE

Be sure to use cables with a sufficiently large cross-

section to avoid excessive line impedance between

the building’s distribution box and the respective

blueplanet unit.

When the line impedance is high, i.e. long AC-side

leads, the voltage at the line terminals of the inverter

will increase as power is being fed in to the grid. The

inverter measures this voltage. If the voltage at the

grid terminals exceeds the line overvoltage limit, the

inverter will switch off due to line overvoltage. This

condition must be taken into consideration when

wiring the AC and dimensioning the AC lead.

!

CAUTION

Check that the leads are properly connected.

ACTION

Once again, ensure that all connected leads are firmly

connected.

PV generator connection

The PV generator leads are connected on the left side

of the inverter.

5.7 Interfaces

All interfaces are connected on the communication circuit

board.

Figure 5.14: Communication circuit board with
highlighted RS485 termination switch

Figure 5.15: Interface terminals

(A) Connecting the fault signal relay

The inverter is equipped with a potential-free relay con-

tact to signal faults. This contact closes if a fault occurs.

The contact is designed as a NO contact and marked

as “ERR” on the circuit board. Maximum contact load

DC: 30 V / 3 A.

AC: 250 V / 1.5 A.

IMPORTANT

In the event of failure of the grid-feed phase (power

failure on the public grid), the relay will not trigger. If this

happens, all LEDs and the display go out. The inverter

is shut down completely. A fault signal cannot be sent.