blueplanet Installation Instructions 1502x - 5002x
6 Two-Stage Shutdown in accordance with IEEE
The shutdown times and the shutdown values for the line voltage and frequency can be narrowed to within a specified
range for the blueplanet 02xi series inverters. The allowed values can be taken from the following tables.
The specifications of the grid operator and the applicable standard must be observed. It is particularly important that
systems < 30 kW comply with the applicable shutdown values for the line frequency.
The clearing time, is the time between the start of the abnormal condition and the inverter stops to feed in.
Voltage – USA 208 V
Voltage range
Clearing time
Undervoltage range 2
104 V * < V < 184 V
0.16 sec (fixed)
Undervoltage range 1
184 V * < V < 208 V
0.16 sec * - 2 sec.
Overvoltage range 1
208 V < V < 228 V *
0.16 sec * - 1 sec.
Overvoltage range 2
228 V < V < 249 V
0.16 sec (fixed)
Voltage – USA 240 V
Voltage range
Clearing time
Undervoltage range 2
120 V * < V < 212 V
0.16 sec (fixed)
Undervoltage range 1
212 V * < V < 240 V
0.16 sec * - 2 sec.
Overvoltage range 1
240 V < V < 264 V *
0.16 sec * - 1 sec.
Overvoltage range 2
264 V < V < 288 V *
0.16 sec (fixed)
Voltage – Mexico 220 V
Voltage range
Clearing time
Undervoltage
198 V *< V < 220 V
0.16 sec (fixed)
Overvoltage
220 V < V < 242 V *
0.16 sec (fixed)
Frequency
Anlage Grösse
Frequency range
Clearing time
Overfrequency range 1
≤ 30 kW
60.0 Hz < f < 60.5 Hz *
0,16 sec (fixed)
Underfrequency range 1
59.3 Hz * < f < 60.0 Hz
0,16 sec (fixed)
Overfrequency range 1
> 30 kW
60.0 Hz < f < 60.5 Hz
0,16 sec (fixed)
Underfrequency range 1
57.0 Hz < f < 59.8 Hz
0,16 sec * - 300 sec.
Underfrequency range 2
f < 57.0 Hz
0,16 sec (fixed)
* = default
Section 6 ·
Two-Stage Shutdown in accordance with IEEE