KACO blueplanet 1502x User Manual
Page 7
blueplanet Installation Instructions 1502x - 5002x
Page 7
Section 3 ·
Technical Data
Inverter – Electrical data
Model
1502x
2502x
3502x
5002x
Max. degree of
efficiency
95.9 % @ 240 V
AC
95.5
% @ 208 V
AC
96.0 % @ 240 V
AC
95.6 % @ 208 V
AC
96.2 % @ 240 V
AC
95.9 % @ 208 V
AC
96.3 % @ 240 V
AC
96.0
% @ 208 V
AC
CEC degree of
efficiency
95.5 % @ 240 V
AC
95.0
% @ 208 V
AC
95.5 % @ 240 V
AC
95 0
% @ 208 V
AC
95.5 % @ 240 V
AC
95.5 % @ 208 V
AC
95.5 % @ 240 V
AC
95.0% @ 208 V
AC
Internal
consumption
Night shutdown: 0.4 W @ 240 V
AC
/ 0.3 W @ 208 V
AC
Operation: < 5 W
Minimum
grid-feed power
10 W
15 W
25 W
25 W
Maximum Output
Fault Current (AC)
and Duration
30 A / 100 µs
50 A / 100 µs
70 A / 100 µs
96 A / 100 µs
Maximum Input
Short Circuit
Current
21.45 A
21.45 A
28.00 A
40.00 A
Maximum Input
Source Backfeed
Current to Input
Source
0 A
Synchronization
In-Rush Current
0 A
Voltage and
Frequency Trip
Time
< 160 ms
Voltage Trip Limit
Accuracy
1.5 % of nominal value
Frequency Trip
Limit Accuracy
± 0.06 Hz
Trip Time
Accuracy
± 0.1 %
Circuit design
Galvanically isolating high frequency DC/DC converter with downstream self-commutated inverter
Clock frequency
17 kHz
Grid monitoring
complies with IEEE 1547