KACO blueplanet 1502x User Manual
Page 13
blueplanet Installation Instructions 1502x - 5002x
Page 13
230.82.6: The type of equipment connected to the
supply is listed, with subsection six identifying solar
electric systems as permissible.
All components within a UL 1741 compliant inverter
must pass evaluation spacing, voltages and currents
that the inverter is rated for. The UL 508 standard,
industrial control equipment, auxiliary devices has
provisions for testing manually operated switches. The
integrated switch passed the UL508 standard under the
file E304888 for use within a UL 1741 approved grid tied
inverter. The switch was tested 6000 operating cycles at
the nominal AC and DC voltages and currents as noted
in table one below. Additional operating cycles of 4000
resulted in a total of 10000 successful operating cycles.
The switch was de constructed and evaluated under a
pass fail criteria.
As referenced in the NEC, subsection 690.17, the switch
must meet applicable voltage and current ratings. The
AC and DC switch ratings are detailed in this table:
AC / DC
Disconnect
Inverter Models
1502x
2502x
3502x
5002x
DC Nominal
Voltage: V
DC
600
550
550
550
550
DC Nominal
Current: I
DC
21.45
21.45
21.45
40
40
AC Nominal
Voltage: V
AC
240/
208
240/
208
240/
208
240/
208
240/
208
AC Nominal
Current: I
AC
8
8
12.5
17
24
The GFDI fuse is located on the bottom plate of the
inverter. When a ground fault occurs this fuse will open
causing the inverter to shut down and indicate a fault.
Replace only with the same type and rating fuse. The
fuse is a fast-acting 600 V
DC
/ 1 A KLKD1 (manufacturer:
littlefuse) rated device.
The night time start switch is located on the bottom
plate of the inverter. Press and hold the start switch for
up to 5 seconds to wake the inverter when there is no
DC input voltage. This allows the user to display the
power that was produced during that day.
Section 5 ·
Installation and Start-Up