blueplanet Operating Instructions 1502x - 5002x

Section 4 ·

Operation

Status

Display

Explanation

10

Temperature too high inside

The temperature in the unit has become too high (> 176 °F). When the internal reaches

158 °F, the inverter limits the power. An internal temperature of 176 °F is only reached if

convection cooling is impeded by external factors, e.g. by covering the cooling fins.

29

Error GFDI - Check Fuse!

A ground fault was detected on the DC side. Notify your authorized electrician so that the

solar generator can be checked.

30

Error Measurement

The current and voltage measurements in the inverter are not plausible. This can be

caused by very dynamic weather conditions if there are quick changes between low grid-

feed power (e.g. 200 W) and high grid-feed power (e.g. the maximum grid-feed power).

32

Error Selftest

The internal grid separation relay test has failed. If this internal error occurs several times,

notify your authorized electrician.

33

Error DC-gridfeeding

The DC feed into the grid has exceeded the permitted limit value. This grid-feed can be

impressed from the grid on the blueplanet inverter so that no inverter fault exists. If this

error occurs several times, notify your authorized electrician.

34

Error Communication

A communication error has occurred in the internal data transmission. If this error occurs

several times, notify the service department.

35

Protection

shutdown

Protection shutdown of the software (AC overvoltage, AC overcurrent, DC link overvolt-

age). This is not an error, but instead a grid-related shutdown.

36

Protection

shutdown HW

Protection shutdown of the hardware (AC overvoltage, AC overcurrent, DC link overvolt-

age). This is not an error, but instead a grid-related shutdown.

38

Failure

PV-Overvoltage

The voltage of the PV generator is too high. The solar generator is wrongly dimensioned.

Notify your authorized electrician.

41

Line failure

Undervoltage

The voltage of the grid-feed phase is too low. The grid cannot be fed into. This error can

be grid-related.

42

Line failure

Overvoltage

The voltage of the grid-feed phase is too high. The grid cannot be fed into. This error can

be grid-related.

48

Line failure

Underfrequency

The line frequency is too low. This error can be grid-related.

49

Line failure

Overfrequency

The line frequency is too high. This error can be grid-related.

50

Line failure average value voltage

The average value of the EN50160 voltage measurement is above the set shut down value.

51

Line failure overvoltage L1

Phase voltage L1 is above the set maximum phase voltage.

52

Line failure undervoltage L1

Phase voltage L1 is below the set maximum phase voltage.

53

Line failure overvoltage L2

Phase voltage L2 is above the set maximum phase voltage.

54

Line failure undervoltage L2

Phase voltage L2 is below the set maximum phase voltage.

55

Error DC link

The voltage at the DC link is too high, or the DC link cannot be charged (IGBT damage).

57

Waiting for reactivation

Waiting for reactivation after an error.

58

Overtemperature

controlling unit

The temperature is too high. To avoid damage, the grid-feed was stopped. Provide for

sufficient ventilation.

59

Error self test

An error occurred during the buffer inspection.

66

Fault in voltage (plausibility error)

Failed plausibility probe of A

DC

-Check between ARM and DSP

Internal error EPROM

An error occurred in the EPROM.

No parameters

Error, no parameters.

Table 4.2:

Fault signals