Emerson Liqui-tect MC68HC16Z1 User Manual
Page 9

Introduction
5
Indicates the operational status of the panel.
Provides the distance liquid is detected, normal
status and cable fault. Used to provide status to a
building management system or remote monitoring
system.
Connecting to a Building Maintenance
System or External Alarm System
Setup System - Setup Alarm Outputs
Provides the distance liquid is detected, normal
status and cable fault. Used to provide status to a
building management system or remote monitoring
system.
Connecting to a Building Maintenance
System or External Alarm System
Setup System - Setup Alarm Outputs
Connection to Liebert leak detection cable.
Connecting Leak Detection Cable
Setup System - Setup ZN2 Zone 2
Connection to Liebert leak detection cable.
Connecting Leak Detection Cable
Setup System - Setup ZN1 Zone 1
Indicates the connection status between the
Liqui-tect panel and an RS232 device.
Connection for a laptop. Used by factory personnel.
Requires a null modem cable for connectivity
(P/N 201258P1).
N/A
Connection to monitor Liqui-tect panel from Liebert’s
SiteScan Web enterprise monitoring system.
Indicates the connection status between the
Liqui-tect panel and SiteScan Web.
Not presently used.
N/A
Not presently used.
N/A
(Transformer Module)
115VAC power receptacle to power laptop during
configuration and diagnostics. Receptacle not
available on 230VAC Transformer Module.
2.4.2: Input and Output Power Connections -
switch (Transformer
Module)
Power switch to turn power On/Off to both
Transformer Module 24VAC connectors and power
receptacle.
2.4.2: Input and Output Power Connections -
(Transformer Module)
One of the two 24VAC connectors for power (the
second is also on the right side of the Transformer
Module near the top). Each connector is rated for
40VA.
2.4.2: Input and Output Power Connections -
Connection for the LCD located on the front door.
N/A
Adjustment contrast for the LCD located on the front
door.
N/A
Reset switch to reset the panel. Same as re-
powering the panel.
N/A
Power connection for the controller. Requires
24VAC.
Connect Power to the Liqui-tect Panel
Transformer Module used to convert 115VAC or
230VAC to 24VAC. Available only in the large
enclosure.
2.4.2: Input and Output Power Connections -
Table 1
Controller board components
Item
Description
More Information