1 view cable status, 1 cable status screens, Viewing additional screens – Emerson Liqui-tect MC68HC16Z1 User Manual
Page 24: Overall condition, Table 5 overall cable conditions, Cable length & current value, View cable status, Cable status screens, Table 5, Overall cable conditions

View Status Options
20
5.1
View Cable Status
The Cable Status screens display the overall status of the cable con-
nected to each of the two zones monitored by the Liqui-tect panel, as
well as the length of the cable being monitored and the amount of cur-
rent present in each cable.
To view the status of the cable:
• From the Main Menu, use the arrows
↑↓
to
choose View Status, as
shown at right, and then press Enter
↵
.
• From the View Status Menu, use the arrows
↑↓
to
choose View
Cable Status and press Enter
↵
.
5.1.1 Cable Status Screens
Each Cable Status screen displays the zone name (
ZN1
or
ZN2
) and its
label (for example,
ZONE 1
or
ZONE 2
) at the top.
Viewing Additional Screens
There are four Cable Status screens—two for each zone.
• To view additional screens, use the arrows
↑↓
.
• To return to the previous screen, press the ESC key.
• When finished viewing the last screen, press Enter
↵
.
Overall Condition
The first screen for each zone shows:
• the zone name (
ZN1
or
ZN2
) and its label (for example,
ZONE 1
or
ZONE 2
)
• the current overall condition of the cable (for example,
NORMAL
)
The cable conditions tracked by the Liqui-tect panel appear in Table 5.
Cable Length & Current Value
The second screen for each zone shows:
• the zone name (
ZN1
or
ZN2
) and its label (for example,
ZONE 1
or
ZONE 2
)
• the length of cable being monitored (for example,
1000FT
)—this value may change dynamically by
up to 0.5% as the panel is continuously calculating the distance of the connected cable
• the current reading (
0UA
, where UA represents µA or microAmps)
Table 5
Overall cable conditions
SOURCE
Cable
CONDITIONS
RECORDED
NORMAL
CABLE BREAK
LEAK DETECTED (& location, e.g., LEAK @ 99 FT)
CONTAMINATED (& location, e.g., CONTAM @ 44 FT)
NOT INSTALLED
Main Menu
> VIEW STATUS
SYSTEM AND CONTROL
↑↓
=NEXT
↵
=SELECT
View Status Menu
> VIEW CABLE STATUS
VIEW ALARM HISTORY
VIEW ZONE TREND
↑↓
=NEXT
↵
=SELECT
Overall Condition (ZN1)
STATUS ZN1 ZONE 1
NORMAL
↑↓
=NEXT
Length & Current (ZN1)
STATUS ZN1 ZONE 1
LENGTH:
1000FT
CURRENT: 0UA
↑↓
=NEXT
↵
=DONE
Overall Condition (ZN2)
STATUS ZN2 ZONE 2
NORMAL
↑↓
=NEXT
Length & Current (ZN2)
STATUS ZN2 ZONE 2
LENGTH:
3500FT
CURRENT: 0UA
↑↓
=NEXT
↵
=DONE