System and Control Options

36

6.8.2 Change Date & Time/Automatic Daylight Saving Time

The Liqui-tect panel has a built-in, real-time clock that is backed up by an encapsulated lithium bat-

tery and set up to adjust automatically for daylight saving time twice a year. The Setup System Info

menu allows you to change the date or time or automatic adjustment at any time.
To change the daylight saving time setting, date or time:

• From the Setup System Info Menu, use the arrows

↑↓

to

choose

Change Date & Time, then press Enter

.

• To change the daylight saving time setting:

• To the right of Daylight Svg Time?

use the arrows

↑↓

to

choose Y (Yes - automatically adjust for daylight saving time)

or N (No), then press Enter

.

• The format of the date and time is DD-MMM-YY HR:MM:SS.

To change the date or time:

• Press Enter

to advance to the next character position you

want to change.

• Use the arrows

↑↓

to

choose from available entries:

• Press Enter

to advance to the next character position.

• When finished, press Enter

again.

6.8.3 Factory Defaults

At any time, you may restore all default values for settings in the

Liqui-tect panel as it was shipped, as shown in Table 12.
The password is the sole exception when reverting to the factory

default settings. The password can be reset to the factory default of

AAAA only through the DIP switches. For details, see Change

Password on page 35.

Date Day (DD)

0-31

Month (MMM) JAN-DEC
Year (YY)

00-99

Time Hour (HR)

00-23

Minutes (MM) 00-59
Seconds (SS) 00-59

Table 12

Factory default settings

Feature

Default

Zones

1 & 2

CONNECTED

N (Not connected)

LABEL

ZONE 1

UNITS

FT (feet)

AUTO CALIBRATE

Automatic

SENSITIVITY FOR

WATER DETECT

150 UA

SENSITIVITY FOR

CONTAMINATED

50 UA

Alarm

outputs

LONGEST CABLE LENGTH

0-1000 ft. (0-304.8m)

LEAK & FAULT RELAYS:

NORMALLY OPEN/CLOSED

NO (Normally Open)

LEAK & FAULT ALARM:

LATCHED/UNLATCHED

Y (Latched)

Mapping

values

Current

0UA, where UA represents µA

or microAmps

Distance

(none)

Re-alarm

delay

Delay in minutes

5 minutes

Setup System Info Menu

SETUP SYSTEM INFO

CHANGE PASSWORD

> CHANGE DATE & TIME

↑↓

=NEXT

=SELECT

FACTORY DEFAULTS

Change Date & Time

CHANGE DATE & TIME

DAYLIGHT SVG TIME? Y

30-APR-03 10:56:30

↑↓

=SELECT

=NEXT/END

Setup System Info Menu

SETUP SYSTEM INFO

CHANGE PASSWORD
CHANGE DATE & TIME

↑↓

=NEXT

=SELECT

> FACTORY DEFAULTS

Factory Defaults

RESTORE ALL DEFAULTS
ARE YOU SURE? Y

↑↓

=Y/N

=END