Multi-function Digital Outputs (Parameters n057 to n059)

When the KEB function is programmed, the Undervoltage detection signal (set value: 15) turns ON

with DC bus voltage less than the KEB Starting Voltage (n048) or during KEB deceleration while the

KEB running signal (set value: 22) turns ON during KEB deceleration or re-acceleration.

The high-speed running signal (set value: 23) is also available. This signal turns ON during speed

agreed of the high (main) speed reference. The high-speed frequency is defined as the reference

when digital input functions Multi-step Speeds 1-3 are OFF (open). The output turns ON/OFF in the

period of 1 second during acceleration or deceleration and in the period of 0.5 second during speed

agreed operation at any frequency reference other than high speed frequency reference, and OFF

during stop.

Mode

High Speed (Main Speed

Frequency Reference Selected)

Low Speed (Any Frequency Reference Other

than Main Speed Frequency Reference)

During Stop

OFF

OFF

During Acceleration or

Deceleration

ON/OFF in period of 1 second

ON/OFF in period of 1 second

During Speed Agreed

ON

ON/OFF in period of 0.5 second

Stall Prevention Deceleration and Braking Transistor Operational Voltage (n049)

If an Overvoltage trip occurs when KEB starts (no braking resistor and stall prevention during

deceleration enabled: n092 = 0), the stall prevention deceleration operational voltage can be

reduced to avoid an OV trip. When several drives are connected on a common DC bus, connect a

braking resistor to the largest drive and refer to monitor display U-05 (DC bus voltage) to adjust this

parameter in order to avoid OV caused by uneven voltage detection.

・Braking transistor operational voltage: DC bus voltage≧n049

・Braking transistor releasing voltage: DC bus voltage≦n049 -10Vdc (20Vdc for 460V units)

AVR Time Constant (Parameter n139)

The time constant of the output voltage AVR (stabilization) function can be adjusted when the output

current or DC bus voltage oscillates during KEB operation. Adjust this parameter in small steps.

When the set value is 0.00sec, the AVR function is disabled.

<1>