2.6 Guidelines of Selection and Adjustment

Regenerative power required to continue operation.(Pm)

Pm (kW) ≧ Load Power (kW) / (Drive Efficiency×Motor Efficiency)

Required deceleration torque (Tm)

Tm (Nm) ≧(60×Pm)×10

3

/[2π×Motor RPM]

Note: Tm must be within the range of motor (drive) stalling torque and overload capacity

Deceleration time (td)

td (sec) ≦ [2πx (Reflected Load Inertia + Motor Inertia)×(Motor RPM)/(60×Tm) ]

Note: In the above equation, Inertia is expressed in kgm

2

Undervoltage (UV1)Trip time at power loss with no KEB (tuv)

tuv (msec) = [Drive Capacity (kW)/Load Power (kW)]×15msec

Required backup capacitor capacity to be added for given backup time (Cb)

Cb (μF) ≧ [(2×P1×10

3

×tb) /(Vn

2

-Vf

2

)×0.9]×10

6

Note: In the above equation;

PI: Load power (kW)

tb: Backup time (sec)

Vn: Main circuit DC bus bar voltage (Vdc)

Vf: Undervoltage (UV1) trip voltage (Vdc)