2. Details of KEB Specification

2.1 Basic Circuit

The KEB function becomes active when parameter n081 (Operation after Recovery from

Momentary Power Loss) is set to 3 (KEB Continuous Operation) or when a multi-function digital

input terminal is set to the KEB command. To restore the motor to the former operation status upon

recovery from a power loss, program one of the multi-function digital input terminals S1 to S7 (n050

to 056) to the KEB command (set values: 28 or 29) as shown in the following table. The run

command must also be maintained during the momentary power loss. When the run command is

removed during the momentary power loss, the drive continues decelerating to a stop even if power

returns.

SA

IM

R

B1

B2

R(L1)

S(L2)

T(L3)

U(T1)

V(T2)

W(T3)

Power Supply

Transformer

S1 Forward Run

S7 KEB Command
n056=××

SC

Regenerative
Energy

・ When regenerative energy is too

large and causes an overvoltage
(OV) trip, connect a braking
resistor.