KEB Command Using Multi-function Digital Input

Programming the KEB command to a multi-function digital input, KEB starts with the KEB Command

OR the drive’s DC bus voltage. The drive specifies the recovery from the power loss when these

signals are restored after the Power Loss Detection Relay Delay Time elapses, and re-accelerates

up to the former speed.

Note: Set KEB Starting Voltage (n048) to a lower value when using the multi-function digital input

KEB command. This will prevent the DC bus voltage detection circuit from activating KEB.

KEB Without a Braking Resistor

Behavior when deceleration stall prevention operates at deceleration (Stall Prevention during

Deceleration Enabled: n092 = 0)

Drive main circuit
DC bus bar voltage

Braking Transistor Operational Voltage or Deceleration
←Stall Prevention Operational Voltage (n049)

Drive output frequency

KEB Starting Voltage→
(n048)

0

Power
loss

During under
voltage detection

OFF

KEB Command

0

n019or n021acceleration ratio

OFF

ON

Power Loss Detection Relay Delay Time (n144)

OFF

OFF

ON

ON

OFF

During KEB
operation

OFF

KEB Deceleration ratio changeover time (n047)

KEB Deceleration Time 1
(n045)

KEB deceleration time 2 (n046)

RUN(FWD) command

ON

KEB Re-acceptance prohibition time (n145)

Drive main circuit
DC bus bar voltage

Drive output frequency

KEB starting voltage→

0

Power Loss

0

When deceleration stall prevention
operates at deceleration

←Braking transistor operation voltage or
deceleration stall prevention operational
voltage(n049)

Deceleration ratio or deceleration time
without KEB function →

Multifun

c

tion

In

p

ut

Mult

ifu

n

ction

Ou

tp

ut

<2> Depending on set value of KEB

re-acceleration time selection (n146)

Power
Recovery