No.

Modbus

Register

Name

Description

Setting

Range

Initial

Value

Remarks

n049 0131H

Stall Prevention

during Deceleration

(and Braking

Transistor

Operational

Voltage)

Sets the Stall Prevention during Decel operational
voltage and the braking transistor turn-on voltage
when a braking resistor is provided.

Note: This function is active regardless of the KEB
function status or programming.

300 to

400Vdc

400Vdc

n139 018BH

AVR Time

Parameter

Sets the time constant of the output voltage AVR
(stabilization) function. AVR function is disabled
when the set value is 0.00sec.

0.00 to

2.55sec

1.00sec

n140 018CH

Undervoltage

Detection Level

Sets the Undervoltage (UV1) trip level of the DC bus.
Normally, this setting does not have to be changed.

Note: This function is active regardless of the KEB
function status or programming.

135 to

210Vdc

150Vdc

The setting range and

the initial value are

doubled for 460V units.

n141 018DH

Operation

Selection at Power

ON

Operation can be prohibited if the run command
(forward or reverse) is present when the power
supply is turned on. This can prevent accidental
machine operation.

0: Run Permitted
1: Run Prohibited

Note: This function is active regardless of the KEB
function status or programming.

0 to 1

0

n142 018EH

Selection of

Transistor

Operation during

Stop

Selects whether the braking transistor circuit is
active when the drive stops.

0: Disabled
1: Enabled

Note: This function is active regardless of the KEB
function status or programming.

0 to 1

0

n143 018FH

KEB Compensation

Time

An Undervoltage (UV1) trip will occur regardless of
the DC bus voltage when a momentary power loss
lasts more than the KEB Compensation Time.

Note: This function is disabled when the set value is
0.00 seconds.

0.0 to

25.5sec

0.0sec

n144 0190H

Power Loss

Detection Relay

Delay Time

Prevents power loss recovery errors caused by a
delay in the opening of the power loss detection
relay by determining when the re-acceleration
sequence is needed. The drive monitors the status
of the KEB Command and the DC bus voltage.

Re-acceleration is made when the multi-function
input terminal and the main circuit DC bus bar
voltage are restored after the power loss detection
relay delay time elapses.

Note: A setting of 50msec will be used when the set
value is 0.0sec.

0.0 to

25.5sec

0.1sec

n145 0191

KEB

Re-acceptance

Prohibition Time

Re-acceptance of KEB operation can be prohibited
only for the specified time after re-acceleration
starts after a momentary power loss.

Note: This function is disabled when the set value is
0.00 seconds.

0.0 to

25.5sec

0.0sec

n146

<2>

0192H

KEB

Re-acceleration

Time selection

Selects the KEB re-acceleration time after the KEB
Command is removed.
0: Selected acceleration time (n019, n021, n041 or

n043)

1: KEB re-acceleration time (n148)

0 to 1

0

n148

<2>

0194H

KEB

Re-acceleration

Time

Sets the KEB re-acceleration time when KEB
re-acceleration time selection (n146) is 1.

Note: This parameter is not effective when n146 is
set to 0.

0.00 to

6000sec

10.0sec