4 keb function related parameters – Yaskawa CIMR-V7AM-091 User Manual

Page 5

background image

Date: 02/20/05, Rev: 05-02

Page 5 of 15

TM.V7SW.091

2.4 KEB Function Related Parameters

No.

Modbus

Register

Name

Description

Setting

Range

Initial

Value

Remarks

n050 to

n056

0132H to

0138H

Multi-function

Digital Input

Selection 1 - 7

Programming the KEB command (settings NO
contact: 28 or NC contact: 29) to a multi-function
digital input enables the KEB function, resulting in
re-acceleration at recovery from the power loss. If a
KEB command is not programmed, operation follows
the setting of parameter n081.

- -

KEB command cannot

be set to more than two

terminals and settings

28 and 29 cannot be

set at the same time.

n057 to

n059

0139H to

013BH

Multi-function
Digital Output

Selection 1 - 3

22: During KEB Operation
KEB signal is output during KEB deceleration or
re-acceleration. This function is not active if the
KEB function is not programmed.

23: High-Speed Operation
This output closes during speed agree the
high-speed (main) frequency selection (when none
of the multi-function digital input functions Multi-step
Speed 1-4 or Jog are closed.).

The output cycles close/open every 0.5 seconds
during speed agree (except for the main speed
reference). The output cycles close/open every 1
second during acceleration or deceleration
regardless of the frequency reference. The output
opens while stopping. This function is active even if
the KEB function is not programmed.

15: Undervoltage Detection
In addition to the standard software conditions of
Undervoltage, the output will also close during
deceleration due to the KEB function.

30: Disturb waveform disable
Signal disables the disturb waveform.

Note: Function available in large HP version only
(VSP01529X).

31: Simple synchronized Accel/Decel
When the signal is input, the Accel/Decel times are
modified as follows:

Time = Accel/Decel time x (Fmax / Fref)

Note: Function available in large HP version only
(VSP01529X).

- -

All multi-function digital

outputs have a

100msec minimum

state length.

n081 0151H

Selection of

Operation after

Momentary Power

Loss

0: Operation not continued.
1: Ride Through. Operation continued at recovery

from power loss within 0.5 second

2: CPU Ride Through. Operation continued at

recovery from power loss (no fault output).

3: KEB Operation.

0 to 3

3

n045 012DH

KEB Deceleration

Time 1

0.00 to

6000 sec

10.0sec

n046 012EH

KEB Deceleration

Time 2

0.00 to

6000sec

10.0sec

n047 012FH

KEB Deceleration

Ratio Changeover

Time

When KEB operation starts, the motor decelerates
in KEB Deceleration Time 1. After KEB
Deceleration Ratio Changeover Time, the motor
decelerates in KEB Deceleration Time 2.
The setting unit of KEB Deceleration Times 1 and 2
depends on the setting of parameter n018:
Accel/Decel Time Setting Unit.

0.00 to

2.55sec

0.10sec

Parameters can be set

during running.

n048 0130H

KEB Starting

Voltage

The drive starts KEB operation when main circuit
DC bus voltage becomes less than the KEB
detection voltage value or when the multi-function
digital input function “KEB Command” is closed.

Note: Parameter n081: Momentary Power Loss

must be set to 3.

135 to

300Vdc

225Vdc

The setting range and

the initial value are

doubled for 460V units.

<1>