Devicenet option error codes, 7 troubleshooting – Yaskawa V1000 Option DeviceNet User Manual

Page 31

background image

7 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 28B V1000 Option DeviceNet Installation Manual

31

DeviceNet Option Error Codes

DeviceNet Option Fault Monitors U6-98 and U6-99

The DeviceNet Option SI-N3/V can declare the error/warning conditions via drive monitor

parameters as shown in

Table 11

.

Table 11 DeviceNet Option Fault Monitor Descriptions

Two drive monitor parameters, U6-99 (OPTN ACTIVE STAT) and U6-98 (OPTN LATCH

STAT) assist the user in network troubleshooting.

• U6-99 displays the present DeviceNet Option SI-N3/V status.

• U6-98 displays the first declared fault since the last fault reset or power cycle.

These parameters are accessible from the DeviceNet network the or the drive digital

operator. A drive fault reset or power off clears and refreshes both U6-99 and U6-98.

Note: In the event of a PLC idle state, the action taken by the DeviceNet Option SI-N3/V is dependent

on the value of parameter F6-54 (Idle Mode Fault Detection).

Fault Condition

Fault

Declared

Status Value

(U6-99/U6-98)

Description

No Fault

n/a

0

No faults.

CPU Error

EF0

1

Option board failure.

PLC in Idle State

EF0

2

PLC is sending polled I/O with all data set to zero.

Force Fault

EF0

3

Network sent a message to force this node to the fault
state.

Network Power Loss

BUS ERROR

1000

Power on DeviceNet network is off.

Connection Time-out

BUS ERROR

1001

This nodes timer (Expect Packet Rate) timed out.

Dup MAC ID

BUS ERROR

1002

This node and at least one other node have the same
MAC ID. Another node sent it’s MAC ID to the
network first.

Bus-Off

BUS ERROR

1003

CAN transceiver senses network error.