7 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 28B V1000 Option DeviceNet Installation Manual

29

Network power loss

The power on the DeviceNet network cable is 0.

• Verify power is available between option terminals V+ (red)

and V- (black).

Connection time-out

The DeviceNet option Expected Packet Rate (EPR) timer timed out.

• Ensure that the EPR time is set properly.

Duplicate MAC ID

The DeviceNet option MAC ID and at least one other mode have the same
MAC ID.

• Verify F6-50 is set properly.

LED Operator Display

Fault Name

EF0

External Fault Input from DeviceNet Option.
The alarm function for an external device is triggered.

Cause

Corrective Action

An external fault is being sent from
the programmable logic controller
(PLC).

• Remove the cause of the external fault.
• Reset the external fault input from the PLC.

Problem with the PLC program.

Check the program used by the PLC and make the appropriate corrections.

The PLC is in Idle mode.

• Change the PLC back to Run mode.
• The DeviceNet option can be made to not declare EF0 when the PLC is in

Idle mode by setting drive parameter F6-54 = 1(no detection).

LED Operator Display

Fault Name

oFA00

DeviceNet Option Fault.
DeviceNet Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to
the drive.

Connect an option that is compatible with the drive.

LED Operator Display

Fault Name

oFA01

DeviceNet Option Fault.
DeviceNet Option is not properly connected.

Cause

Possible Solution

Problem with the connectors between
the drive and DeviceNet Option.

Turn the power off and check the connectors between the drive and
DeviceNet Option.