6 DeviceNet Option Drive Parameters

YASKAWA ELECTRIC TOBP C730600 28B V1000 Option DeviceNet Installation Manual

27

F6-51 Baud Rate

DeviceNet communication speed.

0: 125 kbps

1: 250 kbps

2: 500 kbps

3: Programmable from Network

<6>

4: Detect automatically

<6>

0

<6>

F6-52 PCA setting

<7>

0~255

21

F6-53 PPA setting

<7>

0~255

71

F6-54

Idle Mode Fault
Detection Selection

0: Detection enabled

1: No detection

0

F6-55

<8>

Baud rate from Network 0~2 (Read only)

F6-56 Speed Scaling

-15~15

0

F6-57 Current Scaling

-15~15

0

F6-58 Torque Scaling

-15~15

0

F6-59 Power Scaling

-15~15

0

F6-60 Voltage Scaling

-15~15

0

F6-61 Time Scaling

-15~15

0

F6-62 Heart Beat

0~10

0

F6-63

<8>

MAC ID from Network 0~63 (Read only)

<1> To start and stop the drive with the DeviceNet master device using serial communications, set b1-02 to “3“. To

control the frequency reference of the drive via the master device, set b1-01 to “3”.

<2> If F6-01 is set to 3, then the drive will continue to operate when a Bus error or an EF0 fault is detected. Take

proper safety measures, such as installing an emergency stop switch.

<3> Software versions 1012 and later have F6-07 and F6-08 both set to 1.

<4> All MAC addresses must be unique.

<5> Software version 1011 has a setting range of 0 to 63 with a default value of 63.

<6> F6-51=3 and 4 are not available in software version 1011. Default value is 3.

<7> PCA and PPA will be initialized if unavailable values are set.

<8> F6-55 and F6-63 are not available in software version 1011.