6 DeviceNet Option Drive Parameters
6
DeviceNet Option Drive Parameters
Confirm proper setting of the all parameters in
communications.
Table 9 Parameter Settings
No.
Name
Description
Default
b1-01
Frequency Reference
Selection
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 or d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
1
(Set to 3
for DeviceNet)
b1-02
Run Command
Selection
Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS communications
3: Option PCB
1
(Set to 3
for DeviceNet)
F6-01
Operation Selection
after Communications
Error
Determines drive response when a bUS error is detected during
communications with the DeviceNet Option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
1
F6-02
External Fault Detection
Conditions (EF0)
Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation
0
F6-03
Stopping Method for
External Fault from
Communication Option
Board
Determines drive response for external fault input (EF0) detection
during DeviceNet communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
1
F6-07
NetRef/ComRef
Selection Function
0: Multi-step speed reference disabled
1: Multi-step speed reference allowed
1
F6-08
Reset Communication
Related Parameters
Determines if communication-related parameters F6- and F7-
are set back to original default values when the drive is
initialized using parameter A1-03.
0: Do not reset F6- and F7- parameters.
1: Reset F6- and F7- parameters.
Note: Setting this parameter does not affect communication-
related parameters.
0
F6-50
MAC ID
0~64