Drive Derating Data
Carrier Frequency Derating
The drive can be operated at above the default carrier frequency by derating the drive capacity.
Temperature Derating
To ensure the maximum performance life, the drive output current must be derated as shown in
is installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure
reliable drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.
Parameter Settings
IP00 Enclosure
Drive operation between -10
°C and 50 °C allows 100% continuous current without derating.
IP00 Enclosure with Top Protective Cover
Drive operation between -10
°C and 40 °C allows 100% continuous current without derating. Operation between 40 °C
and 50
°C requires output current derating.
Environment
Area of Use
Indoors
Ambient Temperature
IP00 enclosure with top protective cover: -10 to +40
°C
IP00 enclosure: -10 to +50
°C
Humidity
95 RH% or less (no condensation)
Storage Temperature
-20 to 60
°C (short-term temperature during transportation)
Altitude
Up to 1000 meters without derating, up to 3000 m with output current and voltage derating
Vibration/Shock
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
2
(2A0018 to 2A0225 and 4A0009 to 4A0188) or 2.0 m/s
2
(2A0269 to
2A0432 and 4A0225 to 4A0260)
Standards
• UL Underwriters Laboratories Inc: UL508C Power Conversion Equipment
Protection Design
IP00 enclosure with top protective cover, IP00
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different
motors and with changing motor temperature. Contact Yaskawa for consultation.
<2> Overload protection may be triggered when operating with 133% of the rated output current if the output speed is less than 6 Hz.
<3> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
NOTICE
Refer to the L1000E Quick Start Guide TOEPYAIL1E01 or Technical Manual SIEPYAIL1E01 for more information
regarding the Carrier Frequency Derating and for complete product instructions necessary for proper installation, set
up, troubleshooting and maintenance. The L1000E Series CD-ROM No. CD.L1E.01 packaged with the drive contains
the L1000E Technical Manual No. SIEPYAIL1E01 and additional L1000E Series manuals.
No.
Name
Description
Range
Default
L8-12
Ambient Temperature Setting
Adjust the drive overload (oL2) protection level when the drive is
installed in an environment that exceeds its ambient temperature rating.
-10 to 50
40 °C
L8-35
Installation Method Selection
0: IP00 Enclosure
2: IP00 Enclosure with Top Protective Cover
0 or 2
Determined by
o2-04
Item
Specification