5 Electrical Installation
30
YASKAWA TOEP YAIL1E 02A YASKAWA AC Drive - L1000E Safety Precautions
Serial Communication Terminals
Table 11 Control Circuit Terminals: Serial Communications
MEMOBUS/Modbus Termination
This drive is equipped with a built-in termination resistor for the RS-422/485 communication port. DIP switch S2 enables
or disables the termination resistor as shown in
. The OFF position is the default. The termination resistor
should be placed to the ON position when the drive is the last in a series of slave drives.
Table 12 MEMOBUS/Modbus Switch Settings
Figure 11
Figure 11 DIP Switch S2
Control Circuit Wire Size and Torque Specifications
WARNING! Fire hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in
death or serious injury by fire due to overheating of electrical connections. Improperly tightened terminal screws can also cause
erroneous equipment operation.
Select appropriate wire type and gauges from
. For simpler and more reliable wiring, use crimp ferrules on the
wire ends.
Table 13 Wire Gauges and Torque Specifications
Type
<1> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
No.
Signal Name
Function (Signal Level)
MEMOBUS/Modbus
Communication
R+
Communications input (+)
MEMOBUS/Modbus communication: Use
an RS-485 or RS-422 cable to connect the
drive.
RS-485/422
MEMOBUS/Modbus
communication
protocol
115.2 kbps (max.)
R-
Communications input (-)
S+
Communications output (+)
S-
Communications output (-)
IG
Shield ground
0 V
S2 Position
Description
ON
Internal termination resistor ON
OFF
Internal termination resistor OFF (default setting)
Terminal
Block
Terminal
Size
Tightening
Torque
N•m
(lb.in.)
Bare Wire Terminal
Ferrule-Type Terminal
Applicable
Wire Size
mm
2
(AWG)
Recomm.
mm
2
(AWG)
Applicable
Wire Size
mm
2
(AWG)
Recomm.
mm
2
(AWG)
Wire Type
TB1, TB2,
TB4, TB5,
TB6
FM, AC, AM, P1,
P2, PC, SC, A1,
A2, A3, +V, -V, S1-
S8, MA, MB, MC,
M1, M2, HC, H1,
H2, DM+, DM-, IG,
R+, R-, S+, S-, RP,
MP, E (G)
M2
0.22 to 0.25
(1.9 to 2.2)
Standard wire:
0.25 to 1.0
(24 to 17)
Solid wire:
0.25 to 1.5
(24 to 16)
0.75
(18)
0.25 to 0.5
(24 to 20)
0.5
(20)
Shielded wire,
etc.
DIP Switch S2
(OFF:default)
OFF
ON