Output terminals – Yaskawa AC Drive-L1000E Safety Precautions User Manual
Page 29

5 Electrical Installation
YASKAWA TOEP YAIL1E 02A YASKAWA AC Drive - L1000E Safety Precautions
29
Output Terminals
lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
output.
Note: Multi-function relay output terminals are rated at a minimum of 10 mA. If less than 10 mA is required, use the photocoupler
outputs (P1-C1, P2-C2). Using the wrong current output level may cause the output to malfunction when the terminal is activated.
Table 10 Control Circuit Output Terminals
Figure 10
Figure 10 Connecting a Suppression Diode
H4-07, H4-08: Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Type
<1> Refrain from assigning functions to terminals M1 thru M6 that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Connect a suppression diode as shown in
when driving a reactive load such as a relay coil. Make sure the diode rating is greater than
the circuit voltage.
No.
Terminal Name (Function)
Function (Signal Level) Default Setting
Fault Relay
MA
N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
MB
N.C. output
MC
Fault output common
Multi-Function
Relay Output
M1
Multi-function relay output 1 (Brake release
command)
Contact relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
M2
M3
Multi-function relay output 2 (Output contactor close
command)
M4
M5
Multi-function relay output 3 (Drive ready)
M6
Multi-Function
Photocoupler
Output
P1
Photocoupler output 1 (During Frequency output)
48 Vdc, 2 to 50 mA
C1
P2
Photocoupler output 2 (Not Used/Through Mode)
C2
Monitor Output
FM
Analog monitor output 1 (Output speed)
-10 to +10 Vdc or 0 to +10 Vdc
AM
Analog monitor output 2 (Output current)
AC
Monitor common
0 V
Safety Monitor
Output
DM+ Safety monitor output
Outputs status of Safe Disable function. Closed when both Safe
Disable channels are closed. Up to +48 Vdc 50 mA
DM-
Safety monitor output common
A – External power, 48 V max.
C – Coil
B – Suppression diode
D – 50 mA or less
No.
Parameter Name
Setting Range
Default
H4-07
Terminal FM Signal Level Selection
0 or 1
0
H4-08
Terminal AM Signal Level Selection
0 or 1
0
A
B
C
D