beautypg.com

Introduction – Yaskawa VS-616G5 Profibus-DP Control Card SI-P User Manual

Page 3

background image

VS-616G5 Option Instruction Manual: Profibus-DP Control Card SI-P

Page 3

INTRODUCTION

The Profibus-DP Control Card SI-P is used to connect the VS-616G5 inverter to a Profibus-DP network.
The option card supports 32 bytes of input data, 32 bytes of output data, data transmission rates of up to
12 Mbps, and uses a RS-485 electrical interface.

Description of the Profibus-DP Option Card (SI-P) for the VS-616G5

Name

YEA Code Number

Functions

Profibus-DP
Option Card

SI-P

YAG5-PDP

• Connects inverter to and communicates with a Profibus-DP communication network

.

• Option card plugs into 2CN connector on the control board.
• Option card supports 32 bytes of input data and 32 bytes of output data.
• The card requires VS-616G5 Flash # VSG101042 or higher.

Fig. 1 Profibus-DP Control Card SI-P

Terminal Block TC1

Termination Switch

Address Switch 1 (

×

10)

Address Switch 2 (

×

1)

Indication LED’s

60-pin Connector to

inverter control board (2CN)

Stand-off mounting
hole (4.0mm) dia.

Stand-off mounting
hole (4.0mm) dia.

Grounding lead wire
(connect to terminal #12
of inverter control board)

CODE NO. 73600-C0220

SI-P

YAG5-PDP-T20095