Finish the CM092 EtherNet/IP Option installation.
„

Remove power from the drive and wait for the charge lamp to be
completely extinguished. Wait at least five additional minutes for the
drive to be completely discharged. Measure the DC bus voltage and
verify that it is at a safe level.

„

Reinstall all drive covers and the operator keypad. Apply power to the
drive.

„

Set parameters b1-01 and b1-02 to their appropriate values. Refer to the
table to the right for available b1-01 and b1-02 values.

„

Refer to the appropriate programming or parameter access manual for a
complete list of drive parameters and registers available. A list of
applicable manuals is available at the end of this document.


Param

Function

Data

Description

Default

0 Digital

Operator

1 Terminals
2

Built-in Modbus RTU Terminals

b1-01

Reference

Source

Select

3

Option Card (CM092 EtherNet/IP
Option)

1

0 Digital

Operator

1 Terminals

2

Built-in Modbus RTU Terminals

b1-02

Run

Command

Source

Select

3

Option Card (CM092 EtherNet/IP
Option)

1

‰

Important EtherNet/IP Notes
„

It is strongly recommended that shielded CAT-5 patch or crossover cable be used for all network cables.

„

The maximum number of simultaneous connections are: 1 for I/O, 4 for Explicit, 2 for DriveWizard.

‰

Drive Labeling and EDS Files
„

Place the supplied MAC ID label on the side of the drive either above or below the drive nameplate.

INVERTER MODULE

CODE NO.: EUJ615162

SERV. NO.: 4W06X7847760001

MASS:

125KG

YASKAWA ELECTRONIC AMERICA, INC.

„

To simplify drive configuration, the EDS files can be obtained at

www.yaskawa.com

. Select Downloads, Browse, By Inverter Drives, By Product, and Network

Comms-EtherNet. Then select the appropriate EDS file of the latest version from those listed. EDS files for individual drive models are compressed into a single file
named EDS_AFD_UTC000068_EnetIP_V

_

.zip.

‰

CM092 EtherNet/IP Option Fault Codes
The table of CM092 EtherNet/IP Option fault codes returned by the drive is shown below. Refer to the appropriate drive user and/or programming manual(s) for drive
specific information on the fault returned.

EtherNet/IP Fault Code

[hex]

Description

EtherNet/IP Fault Code

[hex]

Description

0000h None

5300h OPE

errors

(01,02,03,05,06,07,08,09,10,11)

2120h

Ground Fault (GF)

6320h

EEPROM R/W Error (ERR)

2130h

Short Circuit (SC)

7110h

Not Used

2200h

Inverter Overload (OL2)

7112h

Not Used

2220h

Motor Overload (OL1)

7301h

PG Open (PGO)

2221h

Overtorque Detection 1 (OL3)

7310h

Overspeed Detection (OS)

2222h

Overtorque Detection 2 (OL4)

7310h

Speed Deviation (DEV)

2300h Overcurrent

(OC)

7500h EtherNet/IP Communication Error (BUS)

2310h

Not Used

8110h

Feedback Loss (FBL)

3130h

Input Phase Loss (PF)

8313h

Zero Servo Fault (SVE)

3130h

Output Phase Loss (LF)

8321h

Out of Control (CF)

3210h

DC Bus Overvoltage (OV)

8321h

Undertorque Detection 1 (UL3)

3220h

DC Bus Undervoltage (UV1)

8321h

Undertorque Detection 2 (UL4)

3222h

Pre-Charge Contactor Answerback (UV3)

9000h

External Fault 3 (EF3) (Terminal 11)

4200h

Heatsink Over-temperature (OH)

9000h

External Fault 4 (EF4) (Terminal 12)

4210h

Heatsink Maximum Temperature (OH1)

9000h

External Fault 5 (EF5) (Terminal 13)

4300h

Motor Overheat 1 (OH3)

9000h

External Fault 6 (EF6) (Terminal 14)

4310h

Motor Overheat 2 (OH4)

9000h

External Fault 7 (EF7) (Terminal 15)

5110h

Control Power Undervoltage (UV2)

9000h

External Fault 8 (EF8) (Terminal 16)

5120h

DC Bus Fuse Open (PUF)

9000h

External Fault 0 (EF0)

5300h

Operator Disconnected (OPR)

WARNING!

Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.

MAC ID: 00-20-B5-24-11-13