Electronic Lineshaft with Registration

Date: 07/01/04, Rev: 04-07

Sheet 7 of 14

TM.G5SW.047

Trip Reaction

P1-08 = 2

P1-08 Trip

Reaction

Q Q Q Q


If the position error between the master and the follower exceeds the P1-07 setting, the follower responds as selected
below.

Setting Description

0

The follower continues operation without trip annunciation.

1

The follower continues operation while displaying FOL_ALM.

2

The follower faults, coasting to a stop, and displays FOL_FLT.


Resync Property

P1-09 = 1

P1-09 Resynchronization

Property

Q Q Q Q


The follower can be configured to respond to, or ignore, position errors when it is under power, but not running. With a
setting of 0, the follower will monitor the position of both the master and the follower. If a position error develops, via
movement of the master or follower shaft, at the initiation of a run command, the follower will advance or retard
accordingly, to cancel the position error. With a setting of 1, the follower sets the position error to zero, ignoring any
movement of the master or follower that occurred while the follower was stopped.

Setting Description

0

Accumulates position error when not running. Corrects error at ‘run’.

1

Ignores position error when not running. Does not correct at ‘run’.



MOP Rate of Chng

P1-10 = 0.0020

P1-10 MOP Rate of Change per 100ms

Q Q Q Q


A closed digital input to a terminal selected for Raise/Lower Gear Ratio (set value 85/86) will increase or decrease the
gear ratio by P1-10 every 100ms between the master encoder and the follower drive. A digital input to a terminal set to
Reset Gear Ratio (set value 87) will reset the MOP gear ratio back to 1.0000. See P2-01 and P1-02. The MOP function
is multiplied by the preset gear ratio to form the final gear ratio.

Setting Range:

0 to 2

Factory Default:

2 (adjustable while running)

Modbus Address:

0587H

Setting Range:

0 to 1

Factory Default:

1 (adjustable while running)

Modbus Address:

0588H

Setting Range:

0 to 1.0000

Factory Default:

0.0020 (adjustable while running)

Modbus Address:

0589H