Factory Recommended Branch Circuit Protection

Yaskawa recommends installing the following branch circuit protection on each of the 6 phases of the secondary circuit of a

6-Phase/12-Pulse transformer to maintain standards compliance. Semiconductor protective type fuses as listed in

Table 13

are

preferred. Alternate branch circuit protection devices are listed in

Table 14

. Refer to local codes for proper Branch Circuit

Protection on the primary circuit of a 6-Phase/12-Pulse transformer.

NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices

to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.

Table 13 Factory Recommended Drive Branch Circuit Protection

Drive Model

Bussmann Fuse Type

Model

Fuse Ampere Rating (A)

4T0058o

FWH-100B

100

4T0072o

FWH-150B

150

4T0088o

FWH-200B

200

4T0103o

FWH-200B

200

4T0139o

FWH-200B

200

4T0165o

FWH-200B

200

4T0208o

FWH-275A

275

4T0250o

FWH-275A

275

4T0296o

FWH-350A

350

4T0362o

FWH-350A

350

4T0414o

FWH-450A

450

4T0515o

FWH-500A

500

4T0675o

FWH-700A

700

n

Alternative Branch Circuit Protection

The alternative branch circuit protection is time delay fuses. The maximum time delay fuse is 175% of drive input current

rating listed in

Table 14

. This covers any Class J or T fuse.

Table 14 Alternative AC Drive Branch Circuit Protection

Drive Model

Nominal Output Power

kW (HP)

Drive Input Amps/Phase

<1>

Time Delay Fuse Class J or T

Rating Amps Max.

4T0058o

30 (40)

27

45

4T0072o

37 (50)

33

50

4T0088o

45 (60)

39.5

60

4T0103o

55 (75)

48.5

80

4T0139o

75 (100)

65.5

110

4T0165o

90 (125)

78

125

4T0208o

110 (150)

95

150

4T0250o

132 (200)

114

175

4T0296o

160 (250)

137.5

225

4T0362o

185 (300)

158.5

275

4T0414o

220 (350)

188

300

4T0515o

250 (400)

213.5

350

4T0675o

355 (550)

301.5

500

<1> This amp rating is 1/2 rated current because the 3-Phase current is split between 6 input phases for the 6-Phase/12-Pulse drive. Use this amp rating

to select input wiring size as recommended in

Table 5

.

n

Main Circuit Terminal Wiring

Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed

closed-loop crimp terminals are specially required when wiring the drive main circuit terminals. Use only the tools

recommended by the terminal manufacturer for crimping. Refer to

Table 15

for closed-loop crimp terminal recommendations.