Specifications, Power ratings for models 4t0058, 8specifications – Yaskawa A1000 6-Phase/12-Pulse Input User Manual
Page 38

8
Specifications
u
Power Ratings for Models 4T0058o to 4T0208o
Table 8 Power Ratings for Models 4T0058o to 4T0208o
Item
Specification
Drive Model
4T0058o 4T0072o 4T0088o 4T0103o
4T0139o
4T0165o 4T0208o
Maximum Applicable Motor
Capacity kW (HP)
<1>
ND Rating
30
(40)
37
(50)
45
(60)
55
(75)
75
(100)
90
(125)
110
(150)
HD Rating
22
(25-30)
30
(40)
37
(50-60)
45
(50-60)
55
(75)
75
(100)
90
(125-150)
Input
Input Current (A)
<2>
ND Rating
54
66
79
97
131
156
190
HD Rating
40
54
66
79
97
131
156
Rated Voltage
Rated Frequency
6-Phase/12-Pulse: 380 Vac to 480 Vac 50/60 Hz
Note: 6-Phase isolated supply with each of the output windings phase-shifted
by 30 electrical degrees or Hybrid 6-phase topology.
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
53.0
64.9
78.6
96.0
130
156
189
HD Rating
39.3
53.0
64.9
78.6
96.0
130
155
Output
Rated Output
Capacity (kVA)
<3>
ND Rating
<4>
44
55
67
78
106
126
159
HD Rating
34
48
57
69
85
114
137
<6>
Rated Output
Current (A)
ND Rating
<4>
58
72
88
103
139
165
208
HD Rating
45
<5>
60
<5>
75
<5>
91
<5>
112
<5>
150
<6>
180
<6>
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User adjustable between 1 and 15 kHz
User adjustable between
1 and 10 kHz
Maximum Output Voltage (V)
Three-phase: 380 to 480 Vac (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-adjustable)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,
and power supply impedance. This input current rating is the 3-Phase total input current rating.
Refer to Alternative AC Drive Branch Circuit
Protection on page 85
for the 6-Phase input current rating.
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
8 Specifications
38
YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual