Drive Watt Loss Data

Table 10 Drive Watt Loss

Drive Model

Normal Duty

Heavy Duty

Rated

Amps (A)

<3>

Internal

External

Total

Rated

Amps (A)

Internal

External

Total

4T0058o

58

197

453

650

45

<1>

159

341

500

4T0072o

72

244

588

832

60

<1>

206

477

683

4T0088o

88

285

669

954

75

<1>

241

556

797

4T0103o

103

329

827

1156

91

<1>

285

714

999

4T0139o

139

487

1179

1666

112

<1>

447

1100

1547

4T0165o

165

624

1520

2164

150

<2>

629

1647

2276

4T0208o

208

553

1746

2299

180

<2>

586

2199

2765

4T0250o

250

729

2305

3034

216

<2>

663

2308

2971

4T0296o

296

772

2308

3080

260

<2>

694

2295

2989

4T0362o

362

874

3168

4042

304

<2>

788

3075

3863

4T0414o

414

1083

3443

4526

370

<1>

1012

3578

4590

4T0515o

515

1474

4850

6324

450

<1>

1234

3972

5206

4T0675o

675

1789

4861

6650

605

<1>

1504

4191

5695

<1> Value assumes the carrier frequency is set to 8 kHz or less.
<2> Value assumes the carrier frequency is set to 5 kHz or less.
<3> Value assumes the carrier frequency is set to 2 kHz.

u

Drive Derating Data

n

Temperature Derating

To ensure the maximum performance life, the drive output current must be derated as shown in

Figure 21

when the drive is

installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. Set parameter L8-35 to 3

for all 6-Phase/12-Pulse Flange and Non-Flange models to ensure reliable drive overload protection.

n

Parameter Settings

No.

Name

Description

Range

Def.

L8-12

Ambient

Temperature Setting

Adjust the drive overload (oL2) protection level when the drive is installed

in an environment that exceeds its ambient temperature rating.

-10 to +50

+40 °C

L8-35

Installation Method

Selection

0: IP00/Open-Chassis Enclosure

1: Side-by-Side Mounting

2: IP20/NEMA Type 1 Enclosure

3: Finless Drive or External Heatsink Installation

Note:

Set this parameter to 3 for all 6-Phase/12-Pulse Flange and

Non-Flange models.

0 to 3

<1>

<1> Set this parameter to 3 for all 6-Phase/12-Pulse Flange and Non-Flange models. Default setting is determined by drive model.

Setting 0: (Models 4T0208o to 4T0675o)
Setting 2: (Models 4T0058o to 4T0165o).

Setting 0: IP00/Open-Chassis Enclosure

Drive operation between -10 °C and +50 °C allows 100% continuous current without derating.

Setting 1: Side-by-Side Mounting

Drive operation between -10 °C and +30 °C allows 100% continuous current without derating. Operation between +30 °C and

+50 °C requires output current derating.

Setting 2: IP20/NEMA Type 1 Enclosure

Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and

+50 °C requires output current derating.

8 Specifications

42