Drive watt loss data, Drive derating data, Temperature derating – Yaskawa A1000 6-Phase/12-Pulse Input User Manual
Page 42: Parameter settings

u
Drive Watt Loss Data
Table 10 Drive Watt Loss
Drive Model
Normal Duty
Heavy Duty
Rated
Amps (A)
<3>
Internal
External
Total
Rated
Amps (A)
Internal
External
Total
4T0058o
58
197
453
650
45
<1>
159
341
500
4T0072o
72
244
588
832
60
<1>
206
477
683
4T0088o
88
285
669
954
75
<1>
241
556
797
4T0103o
103
329
827
1156
91
<1>
285
714
999
4T0139o
139
487
1179
1666
112
<1>
447
1100
1547
4T0165o
165
624
1520
2164
150
<2>
629
1647
2276
4T0208o
208
553
1746
2299
180
<2>
586
2199
2765
4T0250o
250
729
2305
3034
216
<2>
663
2308
2971
4T0296o
296
772
2308
3080
260
<2>
694
2295
2989
4T0362o
362
874
3168
4042
304
<2>
788
3075
3863
4T0414o
414
1083
3443
4526
370
<1>
1012
3578
4590
4T0515o
515
1474
4850
6324
450
<1>
1234
3972
5206
4T0675o
675
1789
4861
6650
605
<1>
1504
4191
5695
<1> Value assumes the carrier frequency is set to 8 kHz or less.
<2> Value assumes the carrier frequency is set to 5 kHz or less.
<3> Value assumes the carrier frequency is set to 2 kHz.
u
Drive Derating Data
n
Temperature Derating
To ensure the maximum performance life, the drive output current must be derated as shown in
installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. Set parameter L8-35 to 3
for all 6-Phase/12-Pulse Flange and Non-Flange models to ensure reliable drive overload protection.
n
Parameter Settings
No.
Name
Description
Range
Def.
L8-12
Ambient
Temperature Setting
Adjust the drive overload (oL2) protection level when the drive is installed
in an environment that exceeds its ambient temperature rating.
-10 to +50
+40 °C
L8-35
Installation Method
Selection
0: IP00/Open-Chassis Enclosure
1: Side-by-Side Mounting
2: IP20/NEMA Type 1 Enclosure
3: Finless Drive or External Heatsink Installation
Note:
Set this parameter to 3 for all 6-Phase/12-Pulse Flange and
Non-Flange models.
0 to 3
<1>
<1> Set this parameter to 3 for all 6-Phase/12-Pulse Flange and Non-Flange models. Default setting is determined by drive model.
Setting 0: (Models 4T0208o to 4T0675o)
Setting 2: (Models 4T0058o to 4T0165o).
Setting 0: IP00/Open-Chassis Enclosure
Drive operation between -10 °C and +50 °C allows 100% continuous current without derating.
Setting 1: Side-by-Side Mounting
Drive operation between -10 °C and +30 °C allows 100% continuous current without derating. Operation between +30 °C and
+50 °C requires output current derating.
Setting 2: IP20/NEMA Type 1 Enclosure
Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and
+50 °C requires output current derating.
8 Specifications
42