Ul standards – Yaskawa A1000 6-Phase/12-Pulse Input User Manual
Page 84

n
EMC Filters
Install the drive with the EMC filters listed in
to comply with the IEC/EN 61800-3 requirements.
Table 12 IEC/EN 61800-3 Filters
Drive Model
Type
Rated Current
(A)
Weight (lb)
Dimensions
[W x D x H] (in)
Y x X (in)
Qty. per Unit
Manufacturer:
Schaffner
4A0058o
FS5972-35-07
35
4.6
8.1 × 2.0 × 14.0
6.9 × 13.2
2
4A0072o
FS5972-60-07
60
8.8
9.3 × 2.6 × 16.1
8.1 × 15.4
2
4A0088o
4A0103o
4A0139o
FS5972-100-35
100
7.5
3.5 × 5.9 × 13.0
2.6 × 10.0
2
4A0165o
4A0208o
FS5972-130-35
130
10.4
3.5 × 7.1 × 14.6
2.6 × 11.6
2
4A0250o
4A0296o
FS5972-170-40
170
13.2
4.7 × 6.7 × 17.8
4.0 × 14.4
2
4A0362o
FS5972-250-37
250
25.8
5.1 × 9.5 × 24.0
3.5 × 19.6
2
4A0414o
4A0515o
FS5972-410-99
410
23.1
10.2 × 4.5 × 15.2
9.3 × 4.7
2
4A0675o
u
UL Standards
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and
evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL
certification, all components inside that product must also receive UL certification.
Figure 58 UL/cUL Mark
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described
below must be met to maintain compliance when using this drive in combination with other equipment:
n
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
n
Ambient Temperature
Flange Type Enclosure: -10 °C to +40 °C (14 °F to 104 °F)
Non-Flange Type Enclosure: -10 °C to +50 °C (14 °F to 122 °F)
10 Standards Compliance
84
YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual