Wiring checklist, 3 electrical installation – Yaskawa A1000 6-Phase/12-Pulse Input User Manual
Page 24

Drive Model
Terminal
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4T0250o
R/L1, S/L2, T/L3
Refer to applicable codes for wire size
M10
18 to 23
(159.3 to 203.6)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
⊖, ⊕3
22 to 1/0 (0.3 to 53.5)
M6
2.5 to 3.0
(22.1 to 26.6)
Refer to applicable codes for wire size
M10
18 to 23
(159.3 to 203.6)
4T0296o
R/L1, S/L2, T/L3
Refer to applicable codes for wire size
M10
18 to 23
(159.3 to 203.6)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/3
M12
32 to 40
(283.2 to 354.0)
⊖, ⊕3
22 to 1/0 (0.3 to 53.5)
M6
2.5 to 3.0
(22.1 to 26.6)
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
4T0362o
R/L1, S/L2, T/L3
Refer to applicable codes for wire size
M10
18 to 23
(159.3 to 203.6)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
M12
32 to 40
(283.2 to 354.0)
⊖, ⊕3
22 to 1/0 (0.3 to 53.5)
M6
2.5 to 3.0
(22.1 to 26.6)
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
4T0414o
R/L1, S/L2, T/L3
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
⊖, ⊕3
22 to 1/0 (0.3 to 53.5)
M6
2.5 to 3.0
(22.1 to 26.6)
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
4T0515o
R/L1, S/L2, T/L3
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
⊖, ⊕3
13.3 to 127 (6 to 250)
M8
13.5 to 15
(119.5 to 132.8)
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
4T0675o
R/L1, S/L2, T/L3
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
⊖, ⊕3
13.3 to 127 (6 to 250)
M8
13.5 to 15
(119.5 to 132.8)
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
u
Wiring Checklist
No.
Item
Page(s)
Drive, Peripherals, Option Cards
1
Check drive model number to ensure receipt of correct model.
2
Make sure you have the correct braking resistors, DC link chokes, noise filters, and other peripheral devices.
3
Check the option card model number.
Installation Area and Physical Setup
4
Ensure that the area surrounding the drive complies with specifications.
Power Supply Voltage, Output Voltage
3 Electrical Installation
24
YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual