beautypg.com

Yaskawa EtherNet/IP User Manual

Page 44

background image

Fault

Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

Connection

Timeout

BUS ERROR

1101

The node timer (Requested Packet

Interval) timed out.

Duplicate IP

Address

BUS ERROR

1102

This node and at least one other node have

the same IP Address.

Default MAC

Address

None

1103

Factory default MAC Address

programmed into the option. Return for

reprogramming.

Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared

upon drive power-up.

• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset

and upon power-up.

If another fault occurs while the original fault is still active, parameter U6-98 retains the

original fault value and U6-99 stores the new fault status value.

12 Troubleshooting

44

YASKAWA TOEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Installation Manual