beautypg.com

12 troubleshooting – Yaskawa EtherNet/IP User Manual

Page 41

background image

Digital Operator Display

Fault Name

oFb00

Option Card Fault at Option Port CN5-B
Option compatibility error

Cause

Possible Solution

The option card installed into port

CN5-B is incompatible with the

drive

Confirm that the drive supports the option card to be installed.

Refer to Option Compatibility on page 45

for details. Contact Yaskawa for

assistance.

A communication option card has

been installed in option port

CN5-B

Communication option cards are only supported by option port CN5-A. It is not

possible to install more than one communication option.

Digital Operator Display

Fault Name

oFb02

Option Card Fault at Option Port CN5-B
Same type of option card is currently connected

Cause

Possible Solution

An option card of the same type is

already installed in option port

CN5-A

Except for PG options, only one of each option card type can only be installed

simultaneously. Make sure only one type of option card is connected.

Refer to Option Compatibility on page 45

for details. Contact Yaskawa for

assistance.

An input option card is already

installed in option port CN5-A

Install a communication option, a digital input option, or an analog input option.

More than one of the same type of card cannot be installed simultaneously.

Digital Operator Display

Fault Name

oFC00

Option Card Connection Error at Option Port CN5-C
Option compatibility error

Cause

Possible Solution

The option card installed into port

CN5-C is incompatible with the

drive

Confirm that the drive supports the option card to be installed.

Refer to Option Compatibility on page 45

for details. Contact Yaskawa for

assistance.

A communication option card has

been installed in option port

CN5-C

Communication option cards are only supported by option port CN5-A. It is not

possible to install more than one communication option.

Digital Operator Display

Fault Name

oFC02

Option Card Fault at Option Port CN5-C
Same type of option card is currently connected

Cause

Possible Solution

An option card of the same type is

already installed in option port

CN5-A or CN5-B.

Except for PG options, only one of each option card type can only be installed

simultaneously. Make sure only one type of option card is connected.

An input option card is already

installed in option port CN5-A or

CN5-B.

Install a communication option, a digital input option, or an analog input option.

More than one of the same type of card cannot be installed simultaneously.

12 Troubleshooting

YASKAWA TOEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Installation Manual

41