7 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual

31

PG encoder is disconnected or is
not wired properly, or the PG
option or PG encoder are
damaged.

• Rewire the PG encoder and make sure all wiring including shielded wiring is

properly connected.

• If the problem continues after cycling power, replace the PG option or the PG

encoder.

Digital Operator Display

Fault Name

oFA00

Non-Compatible Option connected to drive port CN5-A

Cause

Possible Solution

Non-compatible option
connected to drive port CN5-A.

Use only compatible options. Connect PG-B3 to CN5-B or CN5-C. For other
option, refer to the Installation Manual for that option.

Digital Operator Display

Fault Name

oFb00

Non-Compatible Option connected to drive port CN5-B

Cause

Possible Solution

Non-compatible option
connected to drive port CN5-B.

Use only compatible options. For other option, refer to the Installation Manual for
that option.

Digital Operator Display

Fault Name

oFb01

Option Connection Error at drive port CN5-B

Cause

Possible Solution

Option at drive port CN5-B was
changed during run.

Switch the power off and reconnect the option.

Digital Operator Display

Fault Name

oFC01

Option Connection Error at drive port CN5-C

Cause

Possible Solution

Option at drive port CN5-C was
changed during run.

Switch the power off and reconnect the option.

Digital Operator Display

Fault Name

oS

Overspeed
The motor speed feedback exceeded the F1-08 setting.

Cause

Possible Solution

Overshoot is occurring.

• Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce

C5-02 (Speed Control Integral Time 1).

• Enable Feed Forward Control and perform Inertia Auto-Tuning in CLV.

Incorrect speed feedback scaling
when terminal RP is used as
speed feedback input in V/f
control.

• Set H6-02 to the value of the speed feedback signal frequency when the motor

runs at the maximum speed.

• Adjust the input signal using parameters H6-03 through H6-05.

Incorrect PG encoder pulse
number set.

Check and correct parameter F1-01.

Inappropriate parameter settings.

Check the setting for the overspeed detection level and the overspeed detection
time (F1-08 and F1-09).