6 Related Parameters

28

YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual

F1-31

(3B0)

<2> <7>

PG 2 Pulse
Setting

Sets the pulses to be read from the pulse generator.

V/f w/ PG
CLV

Default: 1024
Min: 0
Max: 60000

F1-32

(3B1)

<7>

PG 2 Rotation

0: Forward = A pulse leads
1: Forward = B pulse leads

V/f w/ PG
CLV

Default: 0
Range: 0, 1

F1-33

(3B2)

<5> <7>

PG 2 Gear
Teeth 1

Number of gear teeth between the PG and motor.

A gear ratio of 1 will be used if any of these
parameters is set to 0.

V/f w/ PG

Default: 0
Min: 0
Max: 1000

F1-34

(3B3)

<5> <7>

PG 2 Gear
Teeth 2

F1-35

(3BE)

<7>

PG 2 Division
Ratio for Pulse
Monitor

Sets the division ratio for PG encoder pulse output.
Set as a three-digit number where x is the first digit, y
is the second digit, and z is the third digit:

When only the A pulse is read, this ratio is disabled
and pulses are set as 1/32 : 1.

V/f w/ PG
CLV

Default: 1
Min: 1
Max: 132

F1-37

(3BD)

<7>

PG 2 Option
Function

0: A pulse detection
1: AB pulse detection

V/f w/ PG

Default: 0
Range: 0, 1

<1> Varies by drive models.

<2> The number of output pulses for the PG encoder can be calculated with the following formula:

<3> The parameter is available only for the drive connector CN5-C.

<4> Value changes according to the control mode selection in A1-02.

<5> Enabled only when using the V/f with PG control mode.

<6> Depending on the drive series, a second PG encoder (PG 2) may not be possible. Refer to the drive Technical

Manual for the drive in your application.

<7> The parameter is available only for the drive connector CN5-B.

No.

(Addr. Hex)

Name

Description

Control

Mode

Values

Pulses

× 60

F1-31

×

F1-33 (load side)

F1-34 (motor side)

Ratio =

(1 + x)

yz

f

PG

(Hz)

Motor speed at maximum frequency output (min

-1

)

60

× PG rating (p/rev)

B3