6 related parameters, Table 7, 6related parameters – Yaskawa 1000 Series Drive Option - Open Collector Type PG User Manual
Page 26
26
YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual
6 Related Parameters
6
Related Parameters
The following parameters set the drive for operation with the option. Set parameters as
needed. Parameter setting methods can be found in the drive Quick Start Guide or Technical
Manual.
Table 7
Related Parameters
No.
(Addr. Hex)
Name
Description
Control
Mode
Values
A1-02
(102)
Control
Method
Selection
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
All Modes
Range:
F1-01
(380)
PG 1 Pulses
per Revolution
Sets the pulses to be read from the pulse generator.
V/f w/ PG
CLV
CLV/PM
Min:
Max:
F1-02
(381)
PG Feedback
Loss Operation
Selection
Sets the stopping method after PG disconnect (PGo).
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
4: No alarm display
NOTICE: Due to potential damage to the motor and
machinery, only use settings 3 and 4 under special
circumstances.
V/f w/ PG
CLV
CLV/PM
F1-03
(382)
PG Overspeed
Operation
Selection
Sets the stopping method after detecting overspeed.
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
NOTICE: Due to potential damage to the motor and
machinery, do not use the "Continue running" setting
except under special circumstances.
V/f w/ PG
CLV
CLV/PM
Default: 1
Range: 0 to 3
F1-04
(383)
PG Deviation
Operation
Selection
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
NOTICE: Due to potential damage to the motor and
machinery, do not use the "Continue running" setting
except under special circumstances.
V/f w/ PG
CLV
CLV/PM
AOLV/PM
Range: 0 to 3
F1-05
(384)
PG 1 Rotation
0: Forward = A pulse leads
1: Forward = B pulse leads
V/f w/ PG
CLV
CLV/PM
Range: 0, 1