beautypg.com

Table 6, 6 related parameters – Yaskawa 1000 Series Drive Option - Digital Output Installation User Manual

Page 24

background image

6 Related Parameters

24

YASKAWA ELECTRIC TOBP C730600 41F 1000-Series Option DO-A3 Installation Manual

Table 6 Binary Coded Output (F5-09 = 1)

Coded Output

Description

TB2

P1-PC

P2-PC

P3-PC

P4-PC

0

Normal operation (no fault)

0

0

0

0

1

oC, GF (Overcurrent)

1

0

0

0

2

ov (Overvoltage)

0

1

0

0

3

oL2 (Unit overload)

1

1

0

0

4

oH, oH1 (Unit overheat)

0

0

1

0

5

oS (Overspeed)

1

0

1

0

6

Not used

0

1

1

0

7

rr, rH (Braking resistor overheat)

1

1

1

0

8

EF1 to EF12 (External fault)

0

0

0

1

9

CPF……, oFA……, oFb……, oFC……
(Unit hardware fault)

1

0

0

1

A

oL1 (Motor overload)

0

1

0

1

B

Not used

1

1

0

1

C

Uv1, Uv2, Uv3 (Undervoltage)

0

0

1

1

D

dEv (Speed deviation)

1

0

1

1

E

PGo (PG disconnect)

0

1

1

1

F

Not used

1

1

1

1