Fer to, Table 4, On p – Yaskawa 1000 Series Drive Option - Digital Output Installation User Manual
Page 20: 5 installation procedure
![background image](https://www.manualsdir.com/files/819209/content/doc020.png)
5 Installation Procedure
20
YASKAWA ELECTRIC TOBP C730600 41F 1000-Series Option DO-A3 Installation Manual
Terminal Functions
Table 4 Option Terminal Functions
Terminal
Block
Terminal
Output
Output Type
Output Level
TB1
<1> Set unit parameters to determine the function assigned to each output. See the unit Instruction Manual for
directions on setting parameters.
M1
Contact relay output 1
N.O. output
Max voltage and current:
250 Vac, 1 A
30 Vdc, 1 A
M2
M3
Contact relay output 2
M4
TB2
P1
Photocoupler output 1
Open-collector output
Max voltage and current:
48 Vdc, 50 mA
P2
Photocoupler output 2
P3
Photocoupler output 3
P4
Photocoupler output 4
P5
Photocoupler output 5
P6
Photocoupler output 6
PC
Photocoupler output common
Emitter common
This manual is related to the following products: