5 Installation Procedure

20

YASKAWA ELECTRIC TOBP C730600 41F 1000-Series Option DO-A3 Installation Manual

Terminal Functions

Table 4 Option Terminal Functions

Terminal

Block

Terminal

Output

<1>

Output Type

Output Level

TB1

<1> Set unit parameters to determine the function assigned to each output. See the unit Instruction Manual for

directions on setting parameters.

M1

Contact relay output 1

N.O. output

Max voltage and current:
250 Vac, 1 A
30 Vdc, 1 A

M2
M3

Contact relay output 2

M4

TB2

P1

Photocoupler output 1

Open-collector output

Max voltage and current:
48 Vdc, 50 mA

P2

Photocoupler output 2

P3

Photocoupler output 3

P4

Photocoupler output 4

P5

Photocoupler output 5

P6

Photocoupler output 6

PC

Photocoupler output common

Emitter common