6 related parameters, Parameter f5-09, 6related parameters – Yaskawa 1000 Series Drive Option - Digital Output Installation User Manual
Page 23
YASKAWA ELECTRIC TOBP C730600 41F 1000-Series Option DO-A3 Installation Manual
23
6 Related Parameters
6
Related Parameters
The parameters outlined in the following sections are used to set up the unit for operation
with the option. Set parameters as needed. Parameter setting methods can be found in the
drive unit Instruction Manual.
◆
Parameter F5-09
Set parameter F5-09 to select the option output mode.
shows the changes in the output terminal contents according to the output mode set
in F5-09.
Table 5 F5-09 and Output Mode
Terminal
Block
Terminal
F5-09 = 0
Individual Output
(Default when Installed to
Drive)
F5-09 = 1
Binary Code Output
F5-09 = 2
Multi-Function Output
(Default when Installed
to Energy-Saving Unit)
TB1
M1-M2
Zero speed
During run
Determined by F5-07
M3-M4
Speed agree
Alarm (excluding bb)
Determined by F5-08
TB2
P1-PC
oC, GF (Overcurrent)
Determined by F5-01
P2-PC
ov (Overvoltage)
Determined by F5-02
P3-PC
oH2 (Unit overheat)
or oL2 (overload)
Determined by F5-03
P4-PC
Not used
Determined by F5-04
P5-PC
oS (Overspeed)
Zero speed
Determined by F5-05
P6-PC
oH, oH1 (Unit overheat)
or oL1 (Overload)
Speed agree
Determined by F5-06