beautypg.com

5 installation procedure – Yaskawa 1000 Series Drive Option - Digital Output Installation User Manual

Page 18

background image

5 Installation Procedure

18

YASKAWA ELECTRIC TOBP C730600 41F 1000-Series Option DO-A3 Installation Manual

5.

Wire the customer-supplied circuit to the terminal blocks on the option. Refer to

Figure 8

for wiring instructions.

Connection Diagram

Refer to

Table 4

on page

20

for a detailed description of the option board terminal

functions. To ensure accurate control, use stable power supply for the voltage

reference source.

Figure 8

Figure 8 Option Connection Diagram

<1> Double-check the polarity on the diode when connecting a DC relay.

<2> Install a surge absorber (SA) when using an AC relay.

Ground wire

CN5-A/
CN5-B/
CN5-C

Unit

DO-A3

TB2

TB1

RLY1

RLY2

RLY3

RLY4

RLY5

RLY6

P1

P2

P4

P3

P5

P6

PC

M1

M2

M4

M3

RLY7

SA

RLY8

SA

DC power supply
(48 V, max.50 mA)

Photocoupler
output

Relay output

AC power supply
(AC250 V, max.1 A)
or
DC power supply
(30 V, max.1 A)

R/L1

S/L2

T/L3

<1>

<2>

FE

Main circuit terminal

Control circuit terminal

DO