6 Related Parameters
24
YASKAWA ELECTRIC
TOBP C730600 43C 1000-Series Option SI-N3 Installation Manual
F6-08
(36A)
Reset Communication
Parameters
Determines which F6- and F7- parameters are reset
to default values when initializing the drive using A1-03.
0: Do not reset parameters
1: Reset parameters
Default: 0
Range: 0, 1
F6-50
(3C1)
DeviceNet MAC ID
Selects the drive MAC address
Note: Used in the DeviceNet Object
Default:
Min: 0
Max: 64
F6-51
(3C2)
DeviceNet
Communication Speed
DeviceNet communication speed
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Programmable from network
4: Auto detect
Note: Used in the DeviceNet Object
Range: 0 to 4
F6-52
(3C3)
DeviceNet PCA Setting I/O Polled Consuming Assembly data instance
Note: Used in the Connection Object
Default: 21
Min: 0
Max: 255
F6-53
(3C4)
DeviceNet PPA Setting
I/O Polled Producing Assembly data instance
Note: Used in the Connection Object
Default: 71
Min: 0
Max: 255
F6-54
(3C5)
DeviceNet Idle Mode
Fault Detection
When detection is enabled and idle messages are detected,
the option will set Run and Frequency to 0.
0: Detection enabled
1: No detection
Default: 0
Range: 0, 1
F6-55
(3C6)
DeviceNet Baud Rate
Monitor
(Read only)
DeviceNet actual communication speed
0: 125 kbps
1: 250 kbps
2: 500 kbps
Note: Used in the DeviceNet Object
Default: 0
Range: 0 to 2
F6-56
(3D7)
DeviceNet Speed
Scaling
Sets the scaling factor for the Speed Monitor in the
DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-57
(3D8)
DeviceNet Current
Scaling
Sets the scaling factor for the Output Current Monitor in the
DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-58
(3D9)
DeviceNet Torque
Scaling
Sets the scaling factor for the Torque Monitor in the
DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15
F6-59
(3DA)
DeviceNet Power
Scaling
Sets the scaling factor for the Power Monitor in the
DeviceNet Object Class 2A hex
Note: Used in the AC/DC Drive Object
Default: 0
Min: -15
Max: 15