Option led display, 4 option components – Yaskawa 1000 Series Drive Option - DeviceNet Installation User Manual
Page 10

4 Option Components
10
YASKAWA ELECTRIC
TOBP C730600 43C 1000-Series Option SI-N3 Installation Manual
◆
Option LED Display
The option has two bicolor, red/green LEDs: one for Module Status (MS) and one for
Network Status (NS).
The operational states of the LEDs after completion of the DeviceNet power-up diagnostic
LED sequence are described in
. Wait at least 2 seconds for the power-up diagnostic
process to complete before verifying the states of the LEDs.
Table 3 Option LED States
Name
Display
Operating Status
Remarks
Color
Status
MS
–
OFF
Power supply OFF
Power is not being supplied to the drive.
Green
ON
Option operating
The option is operating normally.
Green
Flashing Option initializing
There is an incorrect baud rate setting or there is a
MAC ID.
Red
ON
Fatal error occurred
A fatal (irrecoverable) error occurred in the option.
Red
Flashing Non-fatal error occurred
A non-fatal (recoverable) error occurred.
Green/Red Flashing Device self-test
Device in self-test mode.
NS
–
OFF
Offline or Power supply OFF
–
Green
ON
Online communications
established
Device is on-line and has connections in the
established state.
Green
Flashing Online communications not
established
Device is on-line but has no connections in the
established state.
Duplicate MAC ID test has been passed and is on-line
but has no open connections to other nodes.
Red
ON
Communications error
An error occurred disabling DeviceNet
communications.
• MAC ID duplication
• Bus off detected
Red
Flashing Communications time-out
A communications time-out occurred with the master.
Green/Red Flashing Communication faulted
Specific communication faulted device.
• The device has detected a network access error and
is in the communications faulted state.
• The device has then received and accepted an
Identify communication fault request-long protocol
message.