Option mac id, Option baud rate, Eds files – Yaskawa 1000 Series Drive Option - DeviceNet Installation User Manual
Page 22: 5 installation procedure

5 Installation Procedure
22
YASKAWA ELECTRIC
TOBP C730600 43C 1000-Series Option SI-N3 Installation Manual
◆
Option MAC ID
■
Parameter F6-50, MAC ID Setting 0 to 64
The option MAC ID is set with drive parameter F6-50. MAC ID settings between 0~63 are
considered valid MAC IDs; setting 64 indicates a network-settable MAC ID.
The option reads the MAC ID value from F6-50 upon power-up and upon a network reset.
◆
Option Baud Rate
The option supports standard baud rates of 125 kbps, 250 kbps, and 500 kbps.
Table 5 Parameter F6-51 Baud Rate Setting
■
Auto Baud Rate Sensing (F6-51 = 4)
Setting parameter F6-51 to 4 enables automatic baud rate detection and allows the option to
automatically determine the baud rate of the DeviceNet network.
Note: Auto baud rate sensing is valid only when there is more than one node physically on the
DeviceNet network segment. If the auto baud rate sensing fails to detect the baud rate, the drive
digital operator will display “bUS” and the option LEDs will be OFF (NS) and solid green (MS).
◆
EDS Files
To facilitate network implementation, obtain an EDS file from one of the following websites
depending on your region:
US: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: contact a Yaskawa representative.
Description
Value
125 kbps
0
250 kbps
1
500 kbps
2
Programmable from Network
3
Auto Detect
4