Electrical connection

SMA America, LLC

36

ST36-48US-IA-IUS112321

Installation Guide

AC wiring for 277 V/480 V grid configuration

1. Connect the white wire of the AC/DC disconnect to the terminal labeled N and the black wire

to the terminal labeled L1 of the Sunny Boy.

2. For 277 V/480 V connect the blue wire to the terminal labeled PE in the Sunny Boy (not used).

3. Connect the wires to the terminal blocks in the Sunny Boy and tighten to a torque of 18 in lb

(2 Nm).

4. Verify that all connections are correctly wired and properly torqued.

☑ The Sunny Boy is connected to the 277 V/480 V grid.

5. Repeat steps 1 to 4 for the AC wiring of the remaining Sunny Boy inverters.

Position

Description

A

Blue wire connected to PE terminal

B

Black wire connected to L1 terminal

C

White wire connected to N terminal